How to confirm the sizes of flat copper busbar
Standard Copper Bar Current CapacityEstimation method:Single copper bus bar current capacity= width(mm)*thickness coefficientDouble copper bus bar current capacity= width(mm)*thickness coefficient*1.5
Standard Copper Bar Current CapacityEstimation method:Single copper bus bar current capacity= width(mm)*thickness coefficientDouble copper bus bar current capacity= width(mm)*thickness coefficient*1.5
Single copper bus bar current capacity= width(mm)*thickness coefficient
Double copper bus bar current capacity= width(mm)*thickness coefficient*1.5 (empirical coefficient)
Copper bar and aluminum bar can also be estimated as square terms, usually copper should be 5-8A/sq, Aluminum should be 3-5A/sq.
Copper bar current capacity when 40℃ = bar width(mm)*thickness coefficient
(thickness coefficient is 20 when bar width is 12(mm);it is 18 when bar width is 10; it is successively: [12-20,10-18,8-16,6-14,5-13,4-12]
Double copper bars[40℃]=(1.56-1.58)*single copper bar[40℃] (according to the size of section)
Three layers copper bars[40℃]=2*single copper bar[40℃]
Four layers copper bars 40[℃]=2.45*single copper bar[40℃] (not suggested option,replacing with special bus bar is better.)
Copper bar[40℃]=0.85*copper bar[25℃]
Aluminum bar [40℃] =1.3*copper bar[25℃]
For example: To count the 100*10 section copper bar current capacity,
One layer:100*18=1800(A)
Two layers:Current Capacity of 2( 100*10) is :1860*1.58=2940(A)
Three layers:Current Capacity of 3( 100*10) is :1860*2=3720(A)